The fan coil unit is a terminal unit for chilled water and hot water system, such as air cooled and heat pump or water cooled water chiller and heat pump. It mainly consists of fan, cooling coil and casing.
This 1 way cassette fan coil unit is normally installed under the ceiling and supply cool or hot air to wide space with its swings.
1. One Way air flow, which is easy to be installed in the side of ceiling
2. Slim body can be installed in limited space ( Body thickness is 235mm)
3. Remote controller is standard device, wired controller is optional.
4. Auto swing, wide air flowing range, air flowing height up to 3.5m, air delivery angle up to 50o.
5. Horizontal air diffuser can be adjusted by manual.
6. Quiet running
Using double axial extension fan, operation is more stable.
High lift water drained pump (750mm), easy to plan the condensed water drain pipe.
7. Water level switch inside to keep away leakage
After the water raising to a certain position, the float switch will act and alarm, then the unit will cut off the water valve or stop the fan motor. |
![]() ![]() |
8. Fresh air can be input from outside
Fresh air inlet can intake some fresh air from outside and ensure the indoor air quality. The user can share the fresh and clean air to lessen illness caused by air conditioner.
9. Easy installation, low installation cost
No air ducting required, comparing with concealed duct fan coil unit.
10. Fan and fan motor is easy to maintain
2.Easily interfaced with most widely used Modbus and BMS.
3. The water inlet/outlet connection direction (left or right) can be customized.
4.To distinguish t
he water inlet/water outlet pipe of the fan coil unit, will reduce the working hours of piping layout and optimize the space.
5.Water valve can be installed inside of the unit
Water valve is used to control the on/off water flowing to the unit, we install the valve into the unit, so the users do not need to install it by themselves.
6.4 tubes system
There are both cooling and heating water coils inside the unit, so the unit can deal with cooling or heating at the same time.
Table 1 (1 way cassette fan coil unit, 2 pipes type)
Model |
Unit |
BCF34K1 |
BCF51K1 |
BCF68K1 |
BCF85K1 |
||
Power supply |
220V, 1Ph, 50Hz |
||||||
Air flow rate |
H |
m3/h |
340 |
510 |
680 |
850 |
|
M |
280 |
380 |
515 |
660 |
|||
L |
180 |
260 |
340 |
430 |
|||
ESP |
Pa |
0 |
0 |
0 |
0 |
||
Cooling capacity |
TH |
H |
W |
1800 |
2700 |
3600 |
4500 |
SH |
W |
1300 |
1970 |
2700 |
3184 |
||
TH |
M |
W |
1500 |
2460 |
3000 |
3715 |
|
SH |
W |
1000 |
1555 |
1995 |
2420 |
||
TH |
L |
W |
1390 |
2057 |
2479 |
2920 |
|
SH |
W |
823 |
1200 |
1530 |
1825 |
||
Heating capacity |
H |
W |
2700 |
4050 |
5400 |
6750 |
|
M |
W |
1950 |
2770 |
3935 |
4900 |
||
L |
W |
1290 |
1774 |
2800 |
3505 |
||
Noise |
High speed |
dB(A) |
37 |
39 |
41 |
43 |
|
Power input |
W |
37 |
52 |
62 |
76 |
||
water flow |
m3/h |
0.31 |
0.46 |
0.62 |
0.77 |
||
Pressure drop |
kPa |
10.8 |
10.8 |
20 |
20 |
||
Water inlet pipe |
inch |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
||
Water outlet pipe |
inch |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
||
Coil type |
|
Cu/Al |
Cu/Al |
Cu/Al |
Cu/Al |
||
Max. working pressure |
MPa |
1.6 |
1.6 |
1.6 |
1.6 |
||
Drain pipe dia. |
mm |
φ26 |
φ26 |
φ26 |
φ26 |
||
Unit Dimension |
L |
mm |
971 |
971 |
971 |
971 |
|
W |
mm |
413 |
413 |
413 |
413 |
||
H |
mm |
236 |
236 |
236 |
236 |
||
Panel Dimension |
L |
mm |
1044 |
1044 |
1044 |
1044 |
|
W |
mm |
468 |
468 |
468 |
468 |
||
H |
mm |
31 |
31 |
31 |
31 |
||
Net weight |
kg |
26 |
26 |
27 |
27 |
Table 2 (1 way cassette fan coil unit, 4 pipes type)
Model |
Unit |
BCF136K1/4 |
BCF153K1/4 |
BCF170K1/4 |
BCF204K1/4 |
||
Power supply |
220V, 1Ph, 50Hz |
||||||
Air flow rate |
H |
m3/h |
340 |
510 |
680 |
850 |
|
M |
280 |
380 |
515 |
660 |
|||
L |
180 |
260 |
340 |
430 |
|||
ESP |
Pa |
0 |
0 |
0 |
0 |
||
Cooling capacity |
TH |
H |
W |
1350 |
2030 |
2700 |
3380 |
SH |
W |
1000 |
1520 |
2080 |
2450 |
||
TH |
M |
W |
1130 |
1850 |
2250 |
2790 |
|
SH |
W |
770 |
1200 |
1540 |
1860 |
||
TH |
L |
W |
1040 |
1540 |
1860 |
2190 |
|
SH |
W |
630 |
920 |
1180 |
1410 |
||
Heating capacity |
H |
W |
1080 |
1620 |
2160 |
2700 |
|
M |
W |
780 |
1108 |
1574 |
1960 |
||
L |
W |
516 |
710 |
1120 |
1402 |
||
Noise |
High speed |
dB(A) |
43 |
44 |
45 |
46 |
|
Power input |
W |
45 |
60 |
75 |
85 |
||
water flow rate (cooling pipe) (H) |
m3/h |
0.23 |
0.35 |
0.46 |
0.58 |
||
water flow rate (Heating pipe) (H) |
m3/h |
0.09 |
0.14 |
0.19 |
0.23 |
||
Pressure drop |
Cooling pipe |
kPa |
20 |
20 |
20 |
20 |
|
Heating pipe |
kPa |
10 |
10 |
10 |
10 |
||
Cooling water pipe size |
inch |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
ZG3/4″ |
||
Heating water pipe size |
inch |
ZG1/2″ |
ZG1/2″ |
ZG1/2″ |
ZG1/2″ |
||
Coil type |
|
Cu/Al |
Cu/Al |
Cu/Al |
Cu/Al |
||
Max. working pressure |
MPa |
1.6 |
1.6 |
1.6 |
1.6 |
||
Drain pipe dia. |
mm |
φ26 |
φ26 |
φ26 |
φ26 |
||
Unit Dimension |
L |
mm |
958 |
958 |
958 |
958 |
|
W |
mm |
413 |
413 |
413 |
413 |
||
H |
mm |
236 |
236 |
236 |
236 |
||
Panel Dimension |
L |
mm |
1044 |
1044 |
1044 |
1044 |
|
W |
mm |
468 |
468 |
468 |
468 |
||
H |
mm |
31 |
31 |
31 |
31 |
||
Net weight |
kg |
25 |
25 |
26 |
26 |
Notes:
1. Cooling standard condition: Inlet air DB temp. 27℃, WB temp. 19.5℃, water inlet temp. 7 ℃, water outlet temp. 12℃.
2. Heating standard condition: Inlet air DB 21℃, water inlet temp.60 ℃.