Horizontal Ducted Split Unit

123243 app

Ducted Split Unit is a highly efficient and energy saving air conditioning system that applicable to hotel, supermarket, office building, factory, entertainment lieu etc. It combines comfort of central air conditioning with flexibility of split unit. The new design considers the features of modern building, spreading cool/heating air to everywhere of the room equally, to form zero temperature difference. This model occupies less space, integrating duct and indoor decoration, become the upgrade production of central AC and traditional commercial air conditioning.  

fea

1. Wide Range, Various Type

BED indoor series provides various specifications to satisfy residential and commercial application, with electrical heater and fan coil unit, to create a comfortable environment for customer the whole year.

2. Free Application

High static pressure heads making distant air supply realized, convenient for installation. Three-speed drive.
Horizontal airflow of indoor unit, suitable for ceiling installation.

3. Low Noise, Easy Maintenance

Indoor unit can be ceiling-mounted, reducing noise to the lowest level.

High efficiency, low noise centrifugal fan motor, with sound-absorbing and heat preservation material makes low noise operation realized.

4. Intelligent Control

Advanced microcomputer control system with fully automatic control function and protection of high and low pressure, overload, voltage insufficient, phase lack and low temperature, etc.;

Error alarm and display in controller. 

5. Excellent Performance

World famous components, strictly tested to match the unit. Adopting multi-blade pitch centrifugal fan coil, high efficiency compressor, controller, motor. etc. Ensure the stable operation, low vibration and noise.

se

Table 1

Model

Indoor

BED(A)21

BED(A)24

BED(A)28

BED(A)32

BED(A)36

Outdoor

BCN(A)21

BCN(A)24

BCN(A)28

BCN(A)32

BCN(A)36

Cooling capacity

kW

21

23.8

27.6

31.4

35.6

Heating capacity

kW

23.1

26.2

30.3

35.4

40.4

Power input

Cooling

kW

8.1

8.7

11.2

11.6

13.4

Power input

Heating

kW

7.8

8.4

10.8

11.4

13.1

Current input

Cooling

A

15.8

16.16

20.8

21.53

24.89

Current input

Heating

A

14.9

15.56

20.1

21.09

24.23

Refrigerant type

 

R410A

Refrigerant charge amount

Kg

2×2.8

2×3.4

2×4.1

2×4.5

2×5.2

Connect  Pipe

Method

 

welding

Liquid

mm

12.7/12.7

Gas

mm

19.05/19.05

Indoor unit

Air flow

m3/h

4400

4400

4400

5800

6400

ESP

Pa

100

100

100

150

150

Fan

Drive type

 

three speed drive

Dimension

Outdoor

mm

1120x830x1030

1180x960x1130

Indoor

mm

1660x915x480

1660x915x480

Power

Outdoor

 

380V/3Ph/50Hz

Indoor

 

220V/1Ph/50Hz

Noise

Outdoor

dB(A)

60

60

61

61

61

Indoor

dB(A)

55

55

60

60

61

Weight

Outdoor

Kg

180

190

220

240

250

Indoor

Kg

95

105

120

150

160

Condensing pipe

 

G1

G1

G1

G1

G1

Table 2

Model

Indoor

BED(A)48

BED(A)62

BED(A)72

Outdoor

BCN(A)48

BCN(A)62

BCN(A)72

Cooling capacity

kW

47.6

63.5

71.4

Heating capacity

kW

55.2

72.8

80.6

Power input

Cooling

kW

17.7

24.1

26.3

Power input

Heating

kW

17.5

23.3

25.5

Current input

Cooling

A

32.79

44.74

48.82

Current input

Heating

A

32.37

43.23

47.26

Refrigerant type

 

R410A

Refrigerant charge amount

Kg

9+4.5

2×9.5

2×10.5

Connect Pipe

Method

 

welding

Liquid

mm

12.7/15.88

15.88/15.88

15.88/15.88

Gas

mm

19.05/28

28/28

28/28

Indoor unit

Air flow

m3/h

8700

11640

13000

ESP

Pa

200

300

300

Fan

Drive type

 

single speed drive

Dimension

Outdoor

mm

1640x880x1130

1840x970x1130

2120x970x1130

Indoor

mm

2065x1160x680

1870x1230x980

1870x1230x1080

Power

Outdoor

 

380V/3Ph/50Hz

Indoor

 

380V/3Ph/50Hz

Noise

Outdoor

dB(A)

67

67

68

Indoor

dB(A)

63

65

66

Weight

Outdoor

Kg

280

340

460

Indoor

Kg

200

230

300

Condensing pipe

 

G1

G1

G1

Notes:

1. Cooling conditioning: Indoor temperature DB: 27 ℃, WB: 19 ℃; outdoor temperature DB: 35 ℃,WB: 24 ℃.

  1. Heating conditioning: Indoor temperature DB: 20 ℃, WB: 15 ℃; outdoor temperature DB: 7 ℃,WB: 6 ℃.
  2. The static pressure outside is measured under Nominal Airflow.
  3. The data above is obtained from the connection pipe diameter as 7.5m.
WhatsApp Online Chat !